Classification: S90 according to DIN 4102
Approval number: Z-19.15-1560
Installation: square cable fire stops in solid walls and ceilings
HapuflamŽ fire protection mortar
HapuflamŽ fire protection mortar for cable fire stops
Product description
HapuflamŽ fire protection mortar is a dry ready mortar containing all
necessary binders and aggregates in its base mass. The consistency of
the ready fire protection mortar can be moulded and therefore also
inserted as a filler without casing.
Our HauflamŽ fire protection mortar is particularly suited to wall and ceiling openings where the filler thickness is just 20 cm
Our HauflamŽ fire protection mortar is particularly suited to wall and ceiling openings where the filler thickness is just 20 cm
Installation instructions
Before processing, the HapuflamŽ fire protection mortar only needs to be stirred with water to the known plastic consistency.
The prepared HapuflamŽ fire protection mortar can be inserted by hand or, for larger recesses, using a mortar pump and lance.
The prepared HapuflamŽ fire protection mortar can be inserted by hand or, for larger recesses, using a mortar pump and lance.
| Wall thicknesses | Max. filler size | Min. filler depth |
| Masonry > 100mm | 1200 x 2500 | 200 mm |
| Concrete /reinforced concrete > 100mm | 1200 x 2500 | 200 mm |
| Light partition wall > 100mm | 1200 x 2500 | 200 mm |
| Ceiling thicknesses | max. partition size | min. partition size |
| Concrete /reinforced concrete > 160mm | 1000 x ∞ | 200 mm |
Allocation
Cables, steel cable support constructions, aluminium or plastic pipes if
the outer diameter is no more than 15 mm and it is wound with mineral
wool at a length of at least 400 mm in the area of the cable fire stop.
Supply container
- Bucket with 12 kg contents of drying mortar
- Sack goods, contents approximately 20 kg of dry mortar
Mix ratio for small quantities:
1.00 litre dry mortar
+ 0.37 litre water
= 0.82 litre wet mortar