Solid fire stop consisting of fire protection mortar TROMEX or fire protection putty type FTS-K, for separating electrical cables of all types and cables for telecommunications including light wave cables.
Staudt fire protection technology
Cable fire stop S90 / fire protection mortar TROMEX® or fire protection putty type FTS-K
Fire resistance class according to DIN 4102-9:
- S90
- No. Z-19.15-800 fire protection mortar TROMEX
- No. Z-19.15-195 fire protection putty type FTS-K
- Installation in solid walls or ceilings
- Installation in light partition walls (TROMEX only)
Post-installation precautions:
- Fire protection cushions (BSK / St-BSK) or
- post-installation wedges (NIK / UK)
TROMEX® fire protection mortar
S90 universal use cable fire stop. TROMEX fire protection mortar is stirred without adding any additives except for water. For equipping the reserve space with
post-installation wedges NIK (alternatively fire protection cushions).
Partition depth: 200 mm
Partition depth: 200 mm
Fire protection putty TYPE FTS-K
S90 cable fire stop for use in areas with high cleanliness requirements.
The fire protection putty is supplied in a mouldable consistency ready
to use. Equipping the reserves spaces with post-installation wedges UK
(Alternative fire cushions).
Fire stop depth: 200 mm
(Alternative fire cushions).
Fire stop depth: 200 mm
Fire protection cushions
S90 separation of empty and reserve openings that are not yet occupied
by cables, cuboid shaped solid form. Simple handling, laying without
mortar or putty.
Fire protection putty K
Putty
cartridges preferably to separate individual cable recesses, for
post-installation or difficult to access areas.
Combination options
Combination
of fire protection mortar and fire protection cushions or combination
of fire protection putty and fire protection cushions.
Electrical installation channels set
S90 separation with Staudt fire protection putty and arrangement of
post-installation wedges if necessary.
Additional benefits: soundproofing
Additional benefits: soundproofing
Your advantages
- Mechanically steady partitions
- Excellent mounting simplicity
- No post-installation precautions
- No coating of cables and cable trays necessary
- No additional support for cable bearing construction is necessary